A distance relay is set to protect a transmission line with an impedance of =(2+j10)Ω. The relay's Zone 1 is configured to cover 80% of the line's imp
Question

A distance relay is set to protect a transmission line with an impedance of =(2+j10)Ω. The relay's Zone 1 is configured to cover 80% of the line's impedance. What is the apparent impedance measured by the relay during a three-phase fault at the boundary of Zone 1?

A.

Zmeasured =1+j5Ω

B.

Zmeasured =0.4+j2Ω

C.

Zmeasured =2+j10Ω

D.

Zmeasured =1.6+j8Ω

Correct option is D

​Given:∙ Line impedance, Z=2+j10 Ω∙ Zone 1 coverage=80%The impedance measured at the Zone 1 boundary is:Zmeasured=0.8ZZmeasured=0.8(2+j10)Zmeasured=1.6+j8 Ω\begin{aligned}&\textbf{Given:}\\[4pt]&\bullet\ \text{Line impedance, }Z=2+j10\,\Omega\\&\bullet\ \text{Zone 1 coverage}=80\%\\[8pt]&\text{The impedance measured at the Zone 1 boundary is:}\\[4pt]&Z_{\text{measured}}=0.8Z\\[6pt]&Z_{\text{measured}}=0.8(2+j10)\\[6pt]&\boxed{Z_{\text{measured}}=1.6+j8\,\Omega}\end{aligned}​​

test-prime-package

Access ‘SSC JE Electrical Engineering’ Mock Tests with

  • 1.5 Lakhs+ Mocks and Previous Year Papers
  • Unlimited Re-Attempts
  • Personalised Report Card
  • 500% Refund on Final Selection
  • Largest Community
students-icon
589k+ students have already unlocked exclusive benefits with Test Prime!
test-prime-package

Access ‘SSC JE Electrical Engineering’ Mock Tests with

  • 1.5 Lakhs+ Mocks and Previous Year Papers
  • Unlimited Re-Attempts
  • Personalised Report Card
  • 500% Refund on Final Selection
  • Largest Community
students-icon
589k+ students have already unlocked exclusive benefits with Test Prime!
Our Plans
Monthsup-arrow