Correct option is D
A low power factor means that a larger amount of current is required to deliver the same amount of useful (active) power.
The power factor is given by:
Where:
- (P) = Active power (kW)
- (S) = Apparent power (kVA)
- () = Phase angle between voltage and current.
Let us examine each statement.
1. Heat damage to insulation – Correct
- Low power factor increases the current for a given active power.
- Higher current increases copper losses in the system.
- Copper losses are given by ().
- Excessive heating can damage cable and equipment insulation.
2. Increased equipment size – Correct
- Low power factor requires higher current to deliver the same active power.
- Higher current requires larger conductor cross-sections and higher-rated electrical equipment.
- Therefore, the size and rating of transformers, generators, cables and switchgear may increase.
3. Reduced amount of useful power – Correct
- For a given apparent power (kVA) rating, the active power capacity decreases when the power factor decreases.
- Active power is given by:
P=S\cos\phi
- Hence, a low power factor reduces the useful power that can be supplied by equipment of a fixed kVA rating.
4. Voltage fluctuations – Correct
- Higher current due to low power factor increases the voltage drop across the line impedance.
- This can cause poor voltage regulation and greater voltage variations at the load terminals.