    In a brake test, the DC motor took 20 A from a 200 V supply mains. The brake pulley of radius 10 cm had an effective load of 20 kg and the speed was 1
    Question

    In a brake test, the DC motor took 20 A from a 200 V supply mains. The brake pulley of radius 10 cm had an effective load of 20 kg and the speed was 10 rps. The value of BHP (in metric) is _________.

    A.

    0.2π

    B.

    1.3π

    C.

    0.5π

    D.

    8.8π

    Correct option is C

    Given thatI=20 A,V=200 V,r=10 cm=0.1 m,m=20 kg,n=10 r.p.sTorque=Force×Effective radiusT=20×9.81×0.1(F=mg)T=19.62 N ⁣ ⁣mP=T×ωP=T×2πnP=19.62×2×π×10P=392.4π wattP=392.4π735.5 H.P.P=0.5π\text{Given that} \\I = 20\,A, \quad V = 200\,V, \quad r = 10\,cm = 0.1\,m, \quad m = 20\,kg, \quad n = 10\,r.p.s \\[6pt]\text{Torque} = \text{Force} \times \text{Effective radius} \\[6pt]T = 20 \times 9.81 \times 0.1 \quad (\because F = m \cdot g) \\[4pt]T = 19.62\,N\!-\!m \\[8pt]\therefore P = T \times \omega \\[6pt]P = T \times 2\pi n \\[6pt]P = 19.62 \times 2 \times \pi \times 10 \\[6pt]P = 392.4\pi \,\text{watt} \\[6pt]P = \dfrac{392.4\pi}{735.5} \,\text{H.P.} \\[6pt]P = 0.5\pi​​

    test-prime-package

    Access ‘SSC JE Electrical’ Mock Tests with

    • 60000+ Mocks and Previous Year Papers
    • Unlimited Re-Attempts
    • Personalised Report Card
    • 500% Refund on Final Selection
    • Largest Community
    students-icon
    354k+ students have already unlocked exclusive benefits with Test Prime!
    test-prime-package

    Access ‘SSC JE Electrical’ Mock Tests with

    • 60000+ Mocks and Previous Year Papers
    • Unlimited Re-Attempts
    • Personalised Report Card
    • 500% Refund on Final Selection
    • Largest Community
    students-icon
    354k+ students have already unlocked exclusive benefits with Test Prime!
    Our Plans
    Monthsup-arrow